Power

# How much power does a GPU server use?

The number that decides where a GPU server can live. Max draw for every common 8-GPU system, and the cabinet math behind it.

By Mulligan Compute · Updated November 10, 2026

Short answer

An 8-GPU server with PCIe cards like the L40S or RTX PRO 6000 draws about 4 to 6.5 kW at max. HGX systems draw far more: NVIDIA rates the DGX H100 and H200 at about 10.2 kW, the DGX B200 at about 14.3 kW and the DGX B300 at about 14 to 14.5 kW. A standard 208V/30A cabinet circuit gives you about 5 kW to use.

## Max power by system

| System | Max power per GPU | 8-GPU server, max | Fits a 5 kW cabinet? |
| --- | --- | --- | --- |
| 8 × L40S (PCIe) | 350 W | About 4.2 kW | Yes |
| 8 × RTX PRO 6000 Server Edition (PCIe) | 600 W | About 6.2 kW · about 4.6 kW capped at 400 W | Only with GPUs capped |
| 8 × H200 NVL (PCIe) | 600 W | About 6.2 kW | No |
| HGX A100 8-GPU (DGX A100) | 400 W | About 6.5 kW | No |
| HGX H100 / H200 8-GPU (DGX H100 / H200) | 700 W | About 10.2 kW | No |
| HGX B200 8-GPU (DGX B200) | About 1,000 W | About 14.3 kW | No |
| HGX B300 8-GPU (DGX B300) | About 1,400 W | About 14 to 14.5 kW | No |

HGX figures are NVIDIA's DGX system ratings, which include CPUs, NVSwitch, networking and fans. Servers from Supermicro, Dell and HPE with the same GPUs land close to them. PCIe server figures are the GPUs' max power plus about 175 W per GPU for CPUs, memory, drives and fans.

## Where "5 kW" comes from

Most colocation cabinets start with a 208V, 30 amp circuit. Volts times amps gives 6,240 watts. The electrical code limits continuous load to 80% of a circuit, so you can actually use about 5 kW.

| Circuit | Raw capacity | Usable (80%) |
| --- | --- | --- |
| 208V / 30A, single-phase | 6.2 kW | About 5.0 kW |
| 208V / 30A, three-phase | 10.8 kW | About 8.6 kW |
| 208V / 60A, three-phase | 21.6 kW | About 17.3 kW |

Redundant **A+B feeds** don't double that. Each side has to be able to carry the whole load by itself if the other fails, so a cabinet with two 208V/30A feeds still has about 5 kW to use.

## Capping GPU power

Data center GPUs let you set a lower power limit with `nvidia-smi -pl`. Our Node 01 runs its eight RTX PRO 6000 GPUs at 400 W each instead of 600 W, which brings the whole server to about 4.6 kW and fits it in a 5 kW cabinet. Inference gives up some speed at a lower cap; check your own workload before you choose the number.

## Power over a month

A month is about 730 hours. A server running flat out at 6.2 kW uses about 4,500 kWh a month; a DGX B200 at 14.3 kW uses about 10,400 kWh. Colocation is often billed by the kW you reserve per cabinet rather than by kWh, so the max number is the one that sets your bill.

## Cooling

Every watt a server draws turns into heat: 1 kW is about 3,412 BTU per hour. A 10.2 kW HGX H200 server puts out about 34,800 BTU per hour, more than most office server rooms can remove. That is why 8-GPU HGX servers almost always go into a data center.

## What to ask your data center

- How many kW are committed to my cabinet, in writing?
- What voltage, amps and phase are the circuits, and are they A+B?
- How much cooling per cabinet, and is there hot or cold aisle containment?
- Is power billed per kW reserved or per kWh used?

Not sure what fits? Use the [server builder](https://mulligancompute.com/tools/server-builder/) or the [VRAM calculator](https://mulligancompute.com/tools/vram-calculator/); both show the kW.

## Questions

**How much power does an H100 server use?**

An 8-GPU HGX H100 server draws about 10.2 kW at max, per NVIDIA's DGX H100 rating. The H200 version is the same.

**How much power does a B200 server use?**

About 14.3 kW max for an 8-GPU DGX B200, per NVIDIA. The B300 version is about 14 to 14.5 kW.

**How much power does an RTX PRO 6000 server use?**

Eight RTX PRO 6000 Server Edition cards at their full 600 W put a server at about 6.2 kW max. Capped at 400 W each, about 4.6 kW.

**Can I run an 8-GPU server in my office?**

Usually not. Even a PCIe server needs 5 to 6 kW on dedicated 208V circuits plus the cooling to remove that heat. HGX servers need 10 to 14.5 kW. Most go into colocation.

Sources

1. [NVIDIA, DGX B200 specifications (~14.3 kW max)](https://www.nvidia.com/en-us/data-center/dgx-b200/), current
2. [NVIDIA, DGX B300 specifications (~14 kW) and user guide (14.5 kW)](https://docs.nvidia.com/dgx/dgxb300-user-guide/introduction-to-dgxb300.html), current
3. [NVIDIA, DGX H100/H200 user guide (10.2 kW max)](https://docs.nvidia.com/dgx/dgxh100-user-guide/introduction-to-dgxh100.html), current

[Request a quote](https://mulligancompute.com/quote/) · [VRAM calculator](https://mulligancompute.com/tools/vram-calculator/)

On this page

Max power by system · Where "5 kW" comes from · Capping GPU power · Power over a month · Cooling · What to ask your data center · Questions

---

Mulligan Compute. GPU allocation and rental. sales@mulligancompute.com, (636) 248-7171, Franklin, Tennessee (Nashville). Request a quote: https://mulligancompute.com/quote/